17

5 Connecting to power supply

VEGASON 61 • 4 … 20 mA/HART - four-wire

28778-EN-130417

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

Tip:

We recommend using VEGA overvoltage arresters B63-48 and

ÜSB 62-36G.X.
In hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power

supply units.

Supply voltage and current output are carried on separate two-wire

connection cables if reliable separation is required. The supply volt-

age range can differ depending on the instrument version.
The data for power supply are specified in chapter "Technical data".
The standard version can be operated with an earth-connected cur-

rent output, the Exd version must be operated with a floating output.
This instrument is designed in protection class I. To maintain this

protection class, it is absolutely necessary that the ground conductor

be connected to the internal ground terminal. Take note of the general

installation regulations.
Always connect the instrument to vessel ground (potential equalisa-

tion) or in case of plastic vessels to the next ground potential. For

this purpose there is a ground terminal on the side of the instrument

housing.

For power supply, an approved installation cable with PE conductor is

required.
The 4 … 20 mA current output is connected with standard two-wire

cable without screen. If electromagnetic interference is expected

which is above the test values of EN 61326 for industrial areas,

screened cable should be used.
Use cable with round cross-section. A cable outer diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

If you are using cable with a different diameter or cross-section,

exchange the seal or use a suitable cable gland.

If screened cable is necessary, connect the cable screen on both

ends to ground potential. In the sensor, the screen must be connected

directly to the internal ground terminal. The ground terminal on the

outside of the housing must be connected to the potential equalisa-

tion (low impedance).
If potential equalisation currents are expected, the connection on the

processing side must be made via a ceramic capacitor (e. g. 1 nF,

1500 V). The low-frequency potential equalisation currents are thus

Note safety instructions

Take note of safety

instructions for Ex

applications

Voltage supply

Connection cable

Cable screening and

grounding