VEGASON 61 • 4 … 20 mA/HART - four-wire

28778-EN-130417

Ʋ Double chamber housing

– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x

blind plug M20 x 1.5; plug M12 x 1 for VEGADIS 61

(optional)

or:

– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT, plug

M12 x 1 for VEGADIS 61 (optional)

or:

– 1 x plug (depending on the version), 1 x blind plug

M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional)

Spring-loaded terminals for wire cross-

section

< 2.5 mm² (AWG 14)

Display and adjustment module
Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Adjustment elements

4 keys

Protection rating

Ʋ unassembled

IP 20

Ʋ mounted into the sensor without cover IP 40

Material

Ʋ Housing

ABS

Ʋ Inspection window

Polyester foil

Voltage supply
Operating voltage

Ʋ Non-Ex and Ex-d instrument

20 … 72 V DC, 20 … 253 V AC, 50/60 Hz

Power consumption

max. 4 VA; 2.1 W

Electrical protective measures
Protection rating

IP 66/IP 67

Overvoltage category

III

Protection class

I

Functional safety (SIL)
Functional safety is already activated on instruments with SIL qualification ex factory. On instru-

ments without SIL qualification ex factory, the functional safety must be activated by the user via

the display and adjustment module or via PACTware for applications according to SIL.

Functional safety according to IEC 61508-4

Ʋ Single channel architecture (1oo1D) up to SIL2

Ʋ double channel diversitary redundant

architecture (1oo2D)

up to SIL3

You can find detailed information in the supplied Safety Manual of the instrument series or under

"www.vega.com", "Downloads", "Approvals".