VEGA VEGAVIB 63 - Relay (DPDT) User Manual

Page 27

Advertising
background image

Process temperature (thread or flange tem-
perature) with temperature adapter (option)

-50 … +250 °C (-58 … +482 °F)

1

2

3

-50°C

(-58°F)

50°C

(122°F)

40°C

(104°F)

-40°C

(-40°F)

80°C

(176°F)

0°C

(32°F)

100°C

(212°F)

150°C

(302°F)

200°C

(392°F)

250°C

(482°F)

Fig. 26: Ambient temperature - Process temperature

1

Process temperature

2

Ambient temperature

3

Temperature range with temperature adapter

Density

-

Standard

>

0.05 g/cm³ (0.002 lbs/in³)

-

adjustable

>

0.02 g/cm³ (0.0007 lbs/in³)

Granular size

no limitation

1)

Electromechanical data

Cable entry/plug (dependent on the version)

-

Single chamber housing

l

1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5; attached 1 x cable
entry M20 x 1.5

or:

l

1 x cable entry ½ NPT, 1 x blind stopper ½ NPT,
1 x cable entry ½ NPT

or:

l

1 x plug M12 x 1; 1 x blind stopper M20 x 1.5

Spring-loaded terminals

for wire cross-section up to 1.5 mm² (AWG 16)

Adjustment elements

Mode switch

-

Min.

Min. detection or dry run protection

-

Max.

Max. detection or overflow protection

1)

max. 20 mm (0.8 in) with product density < 0.05 g/cm³ (0.002 lbs/in³).

VEGAVIB

63 • - Relay (DPDT)

27

9 Supplement

29277

-

EN

-120418

Advertising