VEGA VEGAVIB 67 - contactless electronic switch User Manual

Page 30

Advertising
background image

>0.02 g/cm³ (>0.0007 lbs/in³)

- adjustable

>0.008 g/cm³ (>0.0003 lbs/in³)

Electromechanical data
Cable entry/plug (dependent on the version)
- Single chamber housing

l

1x cable entry M20x1.5 (cable-ø 5 … 9 mm),

1x blind stopper M20x1.5, attached 1x

cable entry M20x1.5

or:

l

1x cable entry ½ NPT, 1x blind stopper

½ NPT, 1x cable entry ½ NPT

or:

l

1x plug M12x1, 1x blind stopper M20x1.5

Spring-loaded terminals

for wire cross-section up to 1.5 mm²

(0.0023 in²)

Adjustment elements
Mode switch
- min.

min. detection or dry run protection

- max.

max. detection or overfill protection

Voltage supply
Supply voltage

20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

Domestic current requirement

approx. 3 mA (via load circuit)

Load current
- min.

10 mA

- max.

400 mA (at I >300 mA the ambient temperature

can be max. 60 °C/140 °F) max. 4 A up to

40 ms

Electrical protective measures
Protection

IP 66/IP 67

Overvoltage category

III

Protection class

I

Approvals

1)

ATEX II 1/2G, 2G EExd d IIC T6

1)

Deviating data in Ex applications: see separate safety instructions.

Supplement

30

VEGAVIB 67 - with contactless electronic switch

29296

-EN
-060508

Advertising