With solids, you can also choose between "Powder/Dust", "Granular/
Pellets
" or "Ballast/Pebbels".

Through this additional selection, the sensor is adapted perfectly to the
product and measurement reliability, particularly in products with bad
reflective properties, is considerably increased.

Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Apart from the medium, the vessel shape can also influence the
measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or solid
is selected. With "Liquids" these are "Storage tank", "Stilling tube",
"

Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker".

Vessel form

Storage tank

Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e. g. with a cylindrical or
spherical tank - and the indication or output of the volume is required.
Corresponding linearization curves are preprogrammed for these
vessels. They represent the correlation between the level percentage
and vessel volume. By activating the appropriate curve, the volume
percentage of the vessel is displayed correctly. If the volume should
not be displayed in percent but e.g. in l or kg, a scaling can be also set
in the menu item "Display".

Linearisation curve

linear

Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Caution:
Note the following, if VEGAPULS 66 is used as part of an overfill
protection system according to WHG:

If a linearisation curve is selected, the measuring signal is no longer
compulsorily linear proportional to the level. This must be taken into
consideration by the user, particularly when adjusting the switching
point on the level switch.

Vessel form

Linearisation curve

36

VEGAPULS

66 • Profibus PA