4 Mounting

VEGACAL 66 • For connection to a signal conditioning instrument

30321-EN-130917

Insulating measures, such as e.g. covering the thread with teflon tape,

can interrupt the necessary electrical connection with metal vessels.

For this reason, ground the probe on the vessel or use a conductive

seal material.

Metal vessel
Make sure that the mechanical connection of the probe to the vessel

is electrically conductive to ensure sufficient grounding.
Use conductive seals, such as those made of copper or lead, etc.

Insulating measures, such as covering the thread with Teflon tape,

can interrupt the necessary electrical connection with metal vessels.

For this reason, ground the probe on the vessel or use a conductive

seal material.
Non-conductive vessels
In non-conductive vessels, e.g. plastic tanks, the second pole of the

capacitor must be provided separately.

If possible, the capacitive probe should be mounted vertically or par-

allel to the counter electrode. This applies particularly to applications

in non-conductive products.
In cylindrical tanks, spherical tanks or other asymmetrical tank forms,

nonlinear level values are generated due to the varying distance to

the vessel wall.
Use a concentric tube in non-conductive products or linearize the

meas. signal.

4.2 Mounting instructions

During operation, the probe must not touch any installations or the

vessel wall. The measured value can also change if the distance to

the vessel wall changes considerably. If necessary, secure the end of

the probe (insulated).
In the gravity weight there is a thread (M12), e.g. for a ring bolt (op-

tional) - (article no. 2.27424). The gravity weight is isolated from the

measuring cable.
Make sure that the probe cable is not completely taut. Avoid tensile

loads on the cable.

Vessel material

Vessel forms

Installation position