6 Setup with a signal conditioning instrument

VEGACAL 66 • For connection to a signal conditioning instrument

30321-EN-130917

6 Setup with a signal conditioning

instrument

6.1 General information

During setup, the probe must be calibrated with the medium that will

later be measured. To adjust the probe, open the housing cover. You

can select the sensitivity range on the electronics module by means

of the measuring range selection switch.

range 1: 0 … 120 pF

Range 2: 0 … 600 pF

Range 3: 0 … 3000 pF

The adjustment is described in the operating instructions manual of

the respective signal conditioning instrument.

6.2 Adjustment system

1

2

3

Fig. 12: Display and adjustment elements - Oscillator
1 DIL switch for measuring range selection

2 Ground terminal

3 Connection terminals

With the measuring range selection switch (1) you can adapt the

sensitivity of the probe to the electrical properties of the measured

medium and the conditions in the vessel. This is necessary to ensure

that the output current range is a big as possible. The resolution of the

probe is thus also correspondingly increased.
Due to this, the probe can for example also detect products with very

low or very high dielectric constant reliably.

range 1 (sensitive): 0 … 120 pF

range 2 (standard): 0 … 600 pF

range 3 (less sensitive): 0 … 3000 pF

Function/Configuration

Measuring range selec-

tion switch (1)