1application and function, 2technical data – VEGA 9001 Safety barrier User Manual

Page 2

Advertising
background image

2

Safety barrier type 9001

29181-EN-040115

1

Application and function

Safety barrier type 9001 is a passive compo-
nent. With galvanic separation, it converts a
non-intrinsically safe circuit into an intrinsically
safe circuit.

The term „intrinsically safe“ characterizes a
circuit in which the energy flow is limited and
stored capacitive and inductive energy is
secured in such a way that neither switching
operations nor nor short-circuits can ignite an
explosive mixture.

Safety barrier type 9001 takes over this func-
tion. It limits the energy flow, damps the ca-
pacitance C

a

and the inductance L

a

of the

output circuit and reduces the stored energy
reliably. Circuits secured in this way cannot
ignite explosive mixtures.

Operating Instructions

Example:

An indicating instrument is mounted in Ex-
areas and requires an intrinsically safe
0 … 20 mA current signal.

The existing 0 … 20 mA signal to the indicating
instrument however, is not intrinsically safe.
Safety barrier type 9001 is connected to the
signal cable to supply the indicating instru-
ment in Ex-area with an intrinsically safe 20 mA
signal. The safety barrier then provides on its
output an intrinsically safe 0 … 20 mA current
signal for the indicating instrument.

Note:

The capacitance C

a

and inductance L

a

of the

output circuit resulting from the indicating
instrument and the supply cable must not
exceed the stated limit values. The standard
wiring normally ensures these values.

2

Technical data

General

Installation position

outside Ex-area on carrier rail

Operating temperature

-20°C … +60°C

Storage and transport temperature

-20°C … +75°C

Housing material

Polyamide 6 GF

Cross-section area of conductor

1.5 mm

2

(terminals)

Protection acc. to IEC 60529
- terminals

IP 20

- housing

IP 40

Weight

115 g

Approvals
- zone 1

Ex II C 1/2G [EEx ia/ib] IIC/IIB
Ex II 3G EEx ia II T4

- zone 2

[EEx ia] II C / [EEx ia] II B

Input circuit

Nominal voltage U

N

6 V DC

Zener voltage

8.6 V

Min. series resistance

R

min

64 Ohm

Max. series resistance

R

max

73 Ohm

Leakage current against earth at U

N

1 µA

Output circuit

Short-circuit current I

K

150 mA

Capacitance C

a

t EEx ia IIC

6.2 µF

Inductance L

a

at EEx ia IIC

1.3 mH

Capacitance C

a

at EEx ib IIB

55 µF

Inductance L

a

at EEx ib IIB

7 mH

Advertising