4mounting, 3dimensions 5 electrical connection, Operating instructions – VEGA 9001 Safety barrier User Manual
Page 3
Safety barrier type 9001
3
29181-EN-040115
Operating Instructions
4
Mounting
• Mount the safety barrier onto a carrier rail
outside of the hazardous area
• Connect the potential equalisation cable
from the Ex-area to the projecting PA-termi-
nal
• Connect the intrinsically safe circuit (blue)
correctly to the blue-coloured side of the
safety barrier. Note the polarity.
• Now connect the non-intrinsically safe circuit
correctly to the upper white-coloured side of
the safety barrier. Wrong polarity will de-
stroy the safety barrier.
Note:
Cables in Ex-areas must have a durable blue
marking along their entire length.
Non-Ex area
Ex area
3
Dimensions
5
Electrical connection
U
N
0 … 20 mA input
circuit (non-
intrinsically safe)
0 … 20 mA output
circuit (intrinsically
safe)
e.g. indicating instru-
ment
160
16
0
+6 V
086-150-10
9001/01-
4
3
2
1
70
-1
12,2
+0,2
104
-1