1
2
3
4
5
Fig. 9: Connection, valve plug ISO 4400 with IDC crimping technology
1
Compression nut
2
Cable
3
Seal ring
4
Terminal insert
5
Plug housing
For connection to binary inputs of a PLC with an input resistance
<
100 kΩ.
Note:
For inputs with an input resistor > 100 kΩ, the instrument signals
failure.
If the input of the PLC is high-impedance, you have to connect a load
resistor (R
L
) with 100 kΩ according to the following illustration in
parallel to the input of the PLC.
Transistor output
VEGASWING
51 • - transistor (PNP)
17
5 Connecting to power supply
30213
-
EN