6 setup, 1 general information, 2 adjustment elements – VEGA VEGACAP 63 - Relay (DPDT) User Manual

Page 18

Advertising
background image

18

6 Setup

VEGACAP 63 • - Relay (DPDT)

30008-EN-130916

6 Setup

6.1 General information

The figures in brackets refer to the following illustrations.

On the electronics module you will find the following display and

adjustment elements:

Potentiometer for switching point adaptation

DIL switch for measuring range selection

DIL switch for mode adjustment - min./max.

Control lamp

Note:

As a rule, always set the mode with the mode switch (3) before start-

ing setup VEGACAP 63. The switching output will change if you set

the mode switch (3) afterwards. This could possibly trigger other con-

nected instruments or devices.

6.2 Adjustment elements

4

5

6

2

1

3

Fig. 10: Oscillator with relay output
1 Potentiometer for switching point adaptation

2 DIL switch for measuring range selection (with compensation button)

3 DIL switch for mode adjustment

4 Ground terminal

5 Connection terminals

6 Control lamp

The switching status of the electronics can be checked with closed

housing (only plastic housing), see "Function chart".
Note:

Screw the housing cover tightly up to the thread stop so that the

inspection glass is above the control lamp (LED).
To adjust VEGACAP 63, first of all remove the housing cover.

Function/Configuration

Advertising