VEGA VEGACAP 63 - Relay (DPDT) User Manual

Page 29

Advertising
background image

29

9 Supplement

VEGACAP 63 • - Relay (DPDT)

30008-EN-130916

Switching voltage

Ʋ Min.

10 mV

Ʋ Max.

253 V AC, 253 V DC
With circuits > 150 V AC/DC, the relay contacts must be

in the same circuit.

Switching current

Ʋ Min.

10 µA

Ʋ Max.

3 A AC, 1 A DC

Breaking capacity

Ʋ Min.

50 mW

Ʋ Max.

750 VA AC, 54 W DC
If inductive loads or stronger currents are switched

through, the gold plating on the relay contact surface will

be permanently damaged. The contact is then no longer

suitable for switching low-level signal circuits.

Contact material (relay contacts)

AgNi (Au plated) or AgSnO (Au plated)

Modes (switchable)

Min./Max.

Switching delay

Ʋ When immersed

0.7 s

Ʋ When laid bare

0.7 s

Ʋ In case of failure

1 s

Ambient conditions
Ambient temperature on the housing

-40 … +80 °C (-40 … +176 °F)

Storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

Ʋ Threaded versions

-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig), de-

pending on the process fitting

Ʋ Flange version

-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig), de-

pending on the process fitting

Ʋ Flange version ≥ 3"/DN 80, plated

-0.4 … 64 bar/-40 … 6400 kPa (-5.8 … 928 psig), de-

pending on the process fitting

Process temperature VEGACAP 63 of 316L

Ʋ Insulation PE

-40 … +80 °C (-40 … +176 °F)

Ʋ Insulation PTFE

-50 … +150 °C (-58 … +302 °F)

Process temperature (thread or flange

temperature) with temperature adapter

(option with PTFE)

-50 … +200 °C (-58 … +392 °F)