3 function chart – VEGA VEGASWING 61 - contactless electronic switch User Manual

Page 18

Advertising
background image

18

6 Setup

VEGASWING 61 • - contactless electronic switch

29223-EN-130409

"Function chart" (A - max. detection or overflow protection, B - min.

detection or dry run protection).

With this DIL switch (3) you can set the switching point to liquids

having a density between 0.5 and 0.7 g/cm³ (0.018 and 0.025 lbs/

in³). With the basic setting, liquids with a density of > 0.7 g/cm³ (0.025

lbs/in³) can be detected. In liquids with lower density, you must set

the switch to > 0.5 g/cm³ (0.018 lbs/in³). The specifications for the

position of the switching point relate to water - density value 1 g/cm³

(0.036 lbs/in³). In products with a different density, the switching point

will shift in the direction of the housing or tuning fork end depending

on the density and type of installation.
Note:

Keep in mind that foams with a density > 0.45 g/cm³ (0.016 lbs/in³)

are detected by the sensor. This can cause faulty switchings particu-

lary when used as dry run protection system.

6.3 Function chart

The following chart provides an overview of the switching conditions

depending on the set mode and the level.

Level

Switching status

Control lamp

Mode A
Overflow protection

2

1

Switch closed

Green

Mode A
Overflow protection

2

1

Switch open

Red

Mode B
Dry run protection

2

1

Switch closed

Green

Mode B
Dry run protection

2

1

Switch open

Red

Failure of the supply

voltage
(mode A/B)

any

2

1

Switch open

off

Sensitivity adjustment (3)

Advertising