6 Setup with a signal conditioning instrument
VEGACAL 64 • For connection to a signal conditioning instrument
30319-EN-130917
must be as empty as possible for empty adjustment and as full as
possible for full adjustment.
If the indication cannot be set to 100 %, proceed as follows:
If the indication does not reach 100 %, you have to set the range
selection switch on the probe one stage lower.
If the indication exceeds 100 % and cannot be reset, you have to set
the range selection switch of the probe to the next higher stage. In
both cases you have to repeat the adjustment.