8 Maintenance and fault rectification

8.1 Maintenance

When used in the correct way, no special maintenance is required in
normal operation.

8.2 Remove interferences

The operator of the system is responsible for taken suitable measures
to remove interferences.

A maximum of reliability is ensured. Nevertheless, faults can occur
during operation. These may be caused by the following, e.g.:

l

Sensor

l

Process

l

Power supply

l

Signal processing

The first measures to be taken are to check the output signals as well
as to evaluate the error messages via the indicating and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
in this way and faults can be rectified.

However, should these measures not be successful, call the VEGA
service hotline in urgent cases under the phone no. +49 1805 858550.

The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.

?

When an additional instrument is connected, the segment fails.

l

Max. supply current of the segment coupler exceeded

à Measure the current consumption, reduce size of segment

?

Wrong presentation of the measured value in Simatic S5

l

Simatic S5 cannot interpret the number format IEEE of the
measured value

à Insert converting component from Siemens

?

In Simatic S7 the measured value is always presented as 0

l

Only four bytes are consistently loaded in the PLC

à Use function component SFC 14 to load 5 bytes consistently

Reaction when malfunc-
tions occur

Causes of malfunction

Fault rectification