4 setup steps – VEGA VEGAFLEX 67 (-40…+150°C PFA insulated) 4 … 20 mA_HART two-wire User Manual

Page 26

Advertising
background image

6

.4 Setup steps

A

fter connecting VEGAFLEX 67 to power supply or after a voltage

recurrence, the instrument carries out a self-check for approx. 30
seconds:

l

I

nternal check of the electronics

l

I

ndication of the instrument type, the firmware as well as the

sensor TAGs (sensor designation)

l

O

utput signal jumps briefly (approx. 10 seconds) to the set fault

current

T

hen the corresponding current is outputted to the cable (the value

corresponds to the actual level as well as the settings already carried
out, e.g. factory setting).

I

n HART-Multidrop mode (several sensors on one input) the address

must be set before continuing with the parameter adjustment. You will

nd a detailed description in the operating instructions manual

"I

ndicating and adjustment module" or in the online help of PACTware

or DTM.

HART

mode

Standard

Address 0

A

s VEGAFLEX 67 is a distance measuring instrument, the distance

from the sensor to the product surface is measured. To have the real
product level displayed, an allocation of the measured distance to the
percentage height must be made. To carry out this adjustment, the
distance is entered with full and empty vessel. If these values are not
known, an adjustment with the distance values, e.g. 10 % and 90 % is
also possible. Starting point for these distance specifications is always
the seal surface of the thread or flange. With these settings, the real
level is calculated. Furthermore the operating range of the sensor is
limited from maximum to the required range.

T

he real product level during this adjustment is not important, because

the min./max. adjustment is always carried out without changing the
product level. These settings can be made ahead of time without the
instrument having to be installed.

I

n the main menu item "Basic adjustment", the individual submenu

items should be selected one after the other and provided with the
correct parameter values.

S

tart your parameter adjustment with the following menu items of the

basic adjustment:

P

roceed as follows:

Switch-on phase

Address setting HART-
Multidrop

Parameter adjustment

Carry out min. adjust-
ment

26

VEGAFLEX

67 • 4 … 20

mA/HART - two-wire

6 S

et up with the indicating and adjustment module PLICSCOM

32303

-EN

-120329

Advertising