Fig. 23: Measuring ranges of VEGAFLEX 61

1

Reference plane

2

Probe length L

3

Measuring range (default setting refers to the measuring range in water)

4

Upper dead band (see diagrams under Accuracy - grey section)

5

Lower dead band (see diagrams under Accuracy - grey section)

Output variable

Output signal

digital output signal, format according to IEEE-754

Cycle time

min. 1 s (dependent on the parameter setting)

Sensor address

126 (default setting)

Current value

10 mA, ±0.5 mA

Damping (63 % of the input variable)

0 … 999 s, adjustable

Fulfilled NAMUR recommendations

NE

43

Resolution, digital

>

1 mm (0.039 in)

Accuracy (similar to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

+

860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

VEGAFLEX

61 • Profibus PA

47

10 Supplement

31835

-

EN

-100426