VEGA VEGACAL 69 Profibus PA User Manual

Page 42

Advertising
background image

42

10 Supplement

VEGACAL 69 • Profibus PA

31179-EN-130917

– PA-OUT value of the FB1 after scaling

Additional Cyclic Value

– Additional cyclical value (depending on the source)

Free Place

– This module must be used if a value should not be used in the data telegram of the cyclical

data traffic (e.g. replacement of the Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.

Note:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tel-

egram is structured.
Example 1 (standard setting) with distance value and additional cyclical value:

AI (PA-OUT)

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

Status

Status

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

IEEE-754-

Floating point value

Additional Cyclic

Value

Format

Value

Example 2 with distance value without additional cyclical value:

AI (PA-OUT)

Free Place

Byte-No.

1

2

3

4

5

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

Format

Value

Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 28: Data format of the output signal

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded.

The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).
The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.