VEGA VEGACAP 69 - two-wire User Manual

Page 27

Advertising
background image

27

9 Supplement

VEGACAP 69 • - two-wire

31177-EN-130916

Dielectric constant

≥ 1.5

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry/plug

2)

Ʋ Single chamber housing

– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x

blind plug M20 x 1.5

or:

– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT

or:

– 1␣x plug (depending on the version), 1␣x blind stopper

M20␣x␣1.5

Spring-loaded terminals

for wire cross-section up to 1.5 mm² (AWG 16)

Electromechanical data - version IP 66/IP 68 (1 bar)
Cable entry

Ʋ Single chamber housing

– 1 x IP 68 cable gland M20 x 1.5; 1 x blind plug

M20 x 1.5

or:

– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT

Connection cable

Ʋ Wire cross-section

> 0.5 mm² (AWG 20)

Ʋ Wire resistance

< 0.036 Ω/m (0.011 Ω/ft)

Ʋ Tensile strength

< 1200 N (270 lbf)

Ʋ Standard length

5 m (16.4 ft)

Ʋ Max. length

1000 m (3280 ft)

Ʋ Min. bending radius

25 mm (0.984 in) with 25 °C (77 °F)

Ʋ Diameter approx.

8 mm (0.315 in)

Ʋ Colour - standard PE

Black

Ʋ Colour - standard PUR

Blue

Ʋ Colour - Ex-version

Blue

Adjustment elements
DIL switch for measuring range selection

Ʋ range 1

0 … 20 pF

Ʋ range 2

0 … 85 pF

Ʋ range 3

0 … 450 pF

Voltage supply
Operating voltage

10 … 36 V DC (via the signal conditioning instrument)

Electrical protective measures
Protection rating

Ʋ Plastic housing

IP 66/IP 67

2)

Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.