VEGA VEGAFLEX 67 (-40…+150°C) 4 … 20 mA_HART four-wire User Manual

Page 27

Advertising
background image

3

C

onfirm "False signal suppression - Change now" with [OK] and

select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this area
are detected by the sensor and saved after confirming with [OK].

Note:
C

heck the distance to the product surface, because if an incorrect (too

large) value is entered, the existing level will be saved as false signal.
T

he filling level would then no longer be detectable in this area.

T

his function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

T

he following data are read out or written with this function:

l

M

easured value presentation

l

A

djustment

l

M

edium

l

V

essel form

l

D

amping

l

L

inearisation curve

l

S

ensor-TAG

l

D

isplayed value

l

D

isplay unit

l

S

caling

l

C

urrent output

l

U

nit of measurement

l

L

anguage

l

S

ensitivity

l

D

ielectric figure

T

he following safety-relevant data are not read out or written:

l

HART

mode

l

PIN

l

SIL

l

S

ensor length/Sensor type

l

F

alse signal suppression

C

opy sensor data

C

opy sensor data?

Basic adjustment
I

f the function "Reset" is carried out, the sensor resets the values of the

following menu items to the reset values (see chart):

1)

T

he following values will be reset:

1)

S

ensor-specific basic adjustment.

Copy sensor data

Reset

VEGAFLEX

67 • 4 … 20

mA/HART - four-wire

27

6 S

et up with the indicating and adjustment module PLICSCOM

31854

-

EN

-120329