3 function chart – VEGA VEGAWAVE 61 - two-wire User Manual
Page 21
When used on a control system, the following values apply:
l
Mode min.
-
Vibrating element uncovered - 16 mA ±1 mA
-
Vibrating element covered - 8 mA ±1 mA
l
Mode max.
-
Vibrating element uncovered - 8 mA ±1 mA
-
Vibrating element covered - 16 mA ±1 mA
Control lamp for indication of the switching status
l
green = 8 mA
l
red = 16 mA
l
red (flashing) = Failure (< 2.3 mA)
6
.3 Function chart
Level switch VEGAWAVE 61
The following chart provides an overview of the switching conditions
depending on the adjusted mode and level.
Mode on the
sensor
Level
Signal current -
Sensor
Signal lamp -
sensor
Max.
Overflow protec-
tion
8 mA
Green
Max.
Overflow protec-
tion
approx. 16 mA
Red
Min.
Dry run protection
approx. 8 mA
Green
Min.
Dry run protection
approx. 16 mA
Red
Fault message
(min./max. mode)
any
<
2.3 mA
flashes red
Signal lamp (5)
VEGAWAVE
61 • - two-wire
21