4 recurring test and function test (sil) – VEGA VEGAWAVE 61 - two-wire User Manual

Page 22

Advertising
background image

VEGAWAVE 61 level switch with signal conditioning instrument

1

)

The following chart provides an overview of the switching conditions
depending on the adjusted mode of the signal conditioning instrument
and the level.

Note:
Keep in mind that the mode switch of VEGAWAVE 61 must be always
set to "max.".

Mode on the
signal condi-
tioning in-
strument

Level

Signal cur-
rent - Sensor

Signal lamp -
sensor

Signal lamp -
signal condi-
tioning in-
strument

Mode A
Overflow pro-
tection

approx. 8 mA

Green

Mode A
Overflow pro-
tection

approx. 16 mA

Red

Mode B
Dry run pro-
tection

approx. 16 mA

Red

Mode B
Dry run pro-
tection

approx. 8 mA

Green

Fault message
(mode A/B)

any

<

2.3 mA

flashes red

6

.4 Recurring test and function test (SIL)

The VEGAWAVE 61 is qualified for use in measuring chains of level
SIL

2 according to IEC 61508 (redundant, level SIL3).

The measuring system can be used for level detection of bulk solids
and meets the special requirements of safety technology.

1)

You will find suitable signal conditioning instruments in chapter "Technical
data".

General information

SIL

22

VEGAWAVE

61 • - two-wire

6 Set up

32250

-EN

-120418

Advertising