9 Supplement
VEGACAP 69 • - Relay (DPDT)
31175-EN-130916
Ʋ Min.
50 mW
Ʋ Max.
750 VA AC, 54 W DC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact surface will
be permanently damaged. The contact is then no longer
suitable for switching low-level signal circuits.
Contact material (relay contacts)
AgNi (Au plated) or AgSnO (Au plated)
Modes (switchable)
Min./Max.
Switching delay
Ʋ When immersed
0.7 s
Ʋ When laid bare
0.7 s
Ʋ In case of failure
1 s
Ambient conditions
Ambient temperature on the housing
-40 … +80 °C (-40 … +176 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process pressure
-1 … 2 bar/-100 … 200 kPa (-14.5 … 29 psig)
Process temperature
Ʋ Flange of PTFE
-40 … +100 °C (-40 … +212 °F)
Ʋ Flange of PP
0 … +60 °C (+32 … +140 °F)
45°C
100°C
1
-1
0
2
0°C
-40°C
1
2
Fig. 30: Process pressure - Process temperature (flange of PTFE)
1 Process pressure