5 Connecting to power supply

VEGACAP 98 • - Relay (DPDT)

33760-EN-130916

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

Connect the operating voltage according to the following connection

diagrams. The electronics module CAP E31R is designed in protec-

tion class I. To maintain this protection class, it is absolutely neces-

sary that the ground conductor be connected to the internal ground

terminal. Take note of the general installation regulations.
The data for power supply are specified in chapter "Technical data".

The instrument is connected with standard three-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326 for industrial areas, screened cable should

be used.
Use cable with round cross-section. A cable outer diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

If you are using cable with a different diameter or cross-section,

exchange the seal or use a suitable cable gland.
Note:

When placing the housing cover, make sure that the inspection glass

is above the signal lamp of the electronics module.

5.2 Wiring plan, single chamber housing

We recommend connecting VEGACAP 98 in such a way that the

switching circuit is open when there is a level signal, line break or

failure (safe condition).
The relays are always shown in non-operative condition.
The two relays (DPDT) work synchronously. Hence it is possible to

control also e.g. a horn and a magnet valve.

2

3 4 5 6 7

+

L1

N

8

1

1

2

3

Fig. 5: Wiring plan
1 Relay output

2 Relay output

3 Voltage supply

Note safety instructions

Voltage supply

Connection cable

Wiring plan