7 maintenance and fault rectification, 1 maintenance, 2 rectify faults – VEGA VEGACAP 98 - Relay (DPDT) User Manual

Page 17

Advertising
background image

17

7 Maintenance and fault rectification

VEGACAP 98 • - Relay (DPDT)

33760-EN-130916

7 Maintenance and fault rectification

7.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

7.2 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The first measure to be taken is to check the output signal. In many

cases, the causes can be determined this way and the faults rectified.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

Error

Cause

Rectification

– The instrument

signals covered

without cover-

ing with the

medium

– The instrument

signals covered

with cover-

ing with the

medium

Wrong mode se-

lected

Set the correct mode on the mode

switch (A - overflow protection, B - dry

run protection). Wiring should be car-

ried out according to the quiescent

current principle.

Operating voltage

too low

Check operating voltage

Shortcircuit in the

probe, e.g. be-

cause of moisture

in the housing

Remove the electronics module.

Check the resistance between the

marked plug connections. See the fol-

lowing instructions.

Electronics de-

fective

Press the mode switch (A/B). If the in-

strument then changes the mode, the

instrument may be mechanically dam-

aged. Should the switching function in

the correct mode still be faulty, return

the probe for repair.
Push the mode switch. If the probe

then does not change the mode, the

electronics module may be defective.

Exchange the electronics module.

Remove the electronics module. Check the resistance between the

two plug connections.
There must no longer be a connection (high impedance). If there is

still a connection - exchange the instrument or return it for repair

Reaction when malfunc-

tions occur

Reaction when malfunc-

tions occur

Fault rectification

24 hour service hotline

Checking the switching

signal

Check the resistance in

the probe

Advertising