4 recurring function test – VEGA VEGAWAVE 61 - NAMUR User Manual

Page 21

Advertising
background image

Level

Signal current -
Sensor

Control lamp

Falling characteris-
tics max.

2.4 mA

Falling characteris-
tics max.

1 mA

Rising characteris-
tics min.

2.4 mA

Rising characteris-
tics min.

1 mA

Malfunction

any

1 mA

flashes

6

.4 Recurring function test

According to IEC 61508.

VEGAWAVE

61 is qualified in mode A (overfill protection) for use in

measuring chains of stage SIL2 according to IEC 61508 (redundant,
stage SIL3).

The following instrument combinations meet the requirements
according to SIL:

VEGAWAVE

61

l

Oscillator WE60N

The recurring test according to IEC 61508 can be carried out by
pushing the simulation key on the electronics module or by briefly (> 2
seconds) interrupting the cable to the sensor. The correct sequence of
the switching conditions must be monitored via the switching amplifier
as well as the connected systems. The sensor must neither be
removed nor response must be triggered by filling the vessel. This
applies to VEGAWAVE 61 with NAMUR electronics module WE60N.

SIL

Recurring function test

VEGAWAVE

61 • - NAMUR

21

6 Set up

32249

-

EN

-120418

Advertising