2 profibus pa – VEGA VEGACAL 67 Profibus PA User Manual
Page 42
42
10 Supplement
VEGACAL 67 • Profibus PA
31759-EN-130917
Ʋ Aluminium and stainless housing, in-
vestment casting (optionally available)
IP 66/IP 68 (1 bar)
Overvoltage category
III
Protection class
II
10.2 Profibus PA
Instrument master file
The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-
cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-
ment in the configuration tool.
Ident number
Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user
organisation (PNO). This ID number is also included in the name of the GSD file. For VEGACAL 67
the ID number is 0x076E(hex) and the GSD file CL__076E.GSD. Optionally to this manufacturer-
specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGACAL 67
you have to use the general GSD file PA139700.GSD. If the general GSD file is used, the sensor
must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-
ates with the manufacturer-specific ID number.
Cyclical data traffic
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-
tion. The below block diagram below shows which data can be accessed by the PLC.