VEGA VEGAFLEX 67 (-200…+400°C) 4 … 20 mA_HART four-wire User Manual

Page 10

Advertising
background image

TS

d1

h1

h2

d2

1

L2

L1

Fig. 2: Interface measurement

1

Reference plane

d1 Distance to the interface (HART value 1)
d2 Distance to the level (HART value 3)
TS

Thickness of the upper medium (d1 - d2)

h1 Height - Interface
h2 Height - Level
L1

Lower medium

L2

Upper medium

T

he interface is processed directly by the sensor.

T

he analogue output (4 … 20 mA) transmits the height of the interface

(

h1) in percent. This is also the value that is adjusted.

T

he display of PLICSCOM and PACTware outputs the distance to the

interface (d1) in m(d).

T

he HART protocol can transmit the distance to the interface - HART

value 1 (d1) and the distance to the level (d2) - HART value 3.

T

he values can be processed e.g. with a HART interface module (HIM)

or with a VEGAMET 625. VEGAMET 625 can also generate the
difference out of the two values.

F

our-wire electronics with separate power supply.

T

he supply voltage range can differ depending on the instrument

version.

T

he data for power supply are specified in chapter "Technical data".

M

easured value transmission is carried out via the 4 … 20 mA/HART

output separate from power supply.

Output signal

Voltage supply

10

VEGAFLEX

67 • 4 … 20

mA/HART - four-wire