VEGA VEGAWAVE 62 - two-wire User Manual

Page 25

Advertising
background image

signal conditioning instrument). Keep in mind that connected instru-
ments are activated during the function test. By doing this, you can
check the correct function of the measuring system.

Note:
Keep in mind that the starting time t

A

of the voltage supply can extend

the time up to the first switching (e.g. VEGATOR 636: +1 s)

After releasing the button or after a brief line break.

The specified times apply with a tolerance of ±20 %.

Sensor
current -
Sensor

Level relay
A - overfill
protection

Signal
lamp A -
Overfill
protection

Level relay
B - dry run
protection

Signal
lamp B -
Dry run
protection

Fail safe
relay

Control
lamp

1. Fault sig-
nal
approx. 0.6 s
+

t

A

2)

<

2 mA

currentless

currentless

currentless

2. Empty
signal
(approx.
1.5 s)

approx.
8 mA

energized

currentless

energized

3. Full signal
(approx.
1.5 s)

approx.
16 mA

currentless

energized

energized

4. Return to
current ope-
rating condi-
tion

Note:
When used in measuring chains according to IEC 61508, mode B is
not permitted.

Test passed

l

Interference signal (< 3.6 mA) ≥ 400 ms

l

Uncovered (approx. 8 mA) ≥ 1 s

l

Covered (approx. 16 mA) ≥ 1 s

2)

Starting time of the voltage supply

Test procedure

Test assessment (SPLC)

VEGAWAVE

62 • - two-wire

25

6 Set up

32255

-

EN

-120418