5 Connecting to power supply
VEGAPULS SR 68 • Profibus PA
38296-EN-130624
Contact pin
Colour connection ca-
ble in the sensor
Terminal, electronics
module
Pin 1
Brown
5
Pin 2
White
6
Pin 3
Blue
7
Pin 4
Black
8
5.6 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 37: Wire assignment fix-connected connection cable
1 brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.7 Switch-on phase
After VEGAPULS SR 68 is connected to the bus system, the instru-
ment carries out a self-test for approx. 30 seconds. The following
steps are carried out:
•
Internal check of the electronics
•
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
•
Indication of the status message "F 105 Determine measured
value" on the display or PC
•
Status byte goes briefly to fault value
As soon as a plausible measured value is found, it is outputted to the
signal cable. The value corresponds to the actual level as well as the
settings already carried out, e.g. factory settings.