Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 57: Data format of the output signal

The status byte corresponds to profile 3.02 "Profibus PA Profile for Process Control Devices" coded.

The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).
The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.

Byte n

Byte n+1

Bit

7

VZ

Exponent

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Sign

Bit

Significant

7

6

5

4

3

2

1

0

-1

-2

-3

-4

-5

-6

-7

Byte n+2

Byte n+3

Bit

7
2

Significant

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Significant

-9

-10 -11 -12 -13 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23

-8

Value = (-1)

VZ

2

(Exponent - 127)

(1 + Significant)

Fig. 58: Data format of the measured value

Coding of the status byte associated with the PA output value

You can find further information for the coding of the status byte in the Device Description 3.02 on

www.profibus.com.

Status code

Description according to

Profibus standard

Possible cause

0 x 00

bad - non-specific

Flash-Update active

0 x 04

bad - configuration error

– Adjustment error

– Configuration error with PV-Scale (PV-Span too

small)

– Unit irregularity

– Error in the linearization table

0 x 0C

bad - sensor failure

– Hardware error

– Converter error

– Leakage pulse error

– Trigger error

0 x 10

bad - sensor failure

– Measured value generation error

– Temperature measurement error

0 x 1f

bad - out of service con-

stant

"Out of Service" mode switched on

0 x 44

uncertain - last unstable

value

Failsafe replacement value (Failsafe-Mode = "Last val-

ue" and already valid measured value since switching

on)

0 x 48

uncertain substitute set

– Switch on simulation

– Failsafe replacement value (Failsafe-Mode = "Fsafe

value")

0 x 4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid

value" and no valid measured value since switching on)