2 version: capacitive screening, vacuum-tight – VEGA VEGACAP 63 Screening tube adapter Rod ø 16 mm User Manual

Page 4

Advertising
background image

4

2 Mounting

Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63

34849-EN-130916

4. Screw the screening tube adapter (3) onto the thread of the probe

and tighten with 100 Nm (74 lbf ft) (SW 46)

The mounting of the screening tube adapter is now finished. The

probe can now be installed.
You can find the mounting procedure in the operating instructions of

the probe.
Note:

The VEGACAP probe must be re-compensated after mounting the

screening tube adapter. Use the compensation key on the electronics

module. You can find the instructions for this in the operating instruc-

tions of the probe.

2.2 Version: capacitive screening, vacuum-tight

1

2

3

4
5

Fig. 2: Mounting of the screening tube adapter - capacitive screening, vacuum-

tight
1 Probe

2 Process seal

3 Screening tube adapter

4 O-rings (2 pcs.)

5 Pressure screw

Advertising