background image

10

4 Setup

Antenna extension up to 450 °C • for VEGAPULS 62 and 68

38316-EN-131119

4 Setup

When the antenna extension is delivered with the radar sensor, a

false signal fade-out is carried out beforehand at the factory. False

echoes caused by the antenna extension are thus eliminated in the

signal processing system.
The false echo curve of a retrofitted antenna extension must be called

up and checked via a PC with PACTware. If assembly is correct, the

red echo curve will lie directly on top of the blue false echo curve. It

is generally recommended that the user carry out a false signal sup-

pression before setup.

When using an antenna extension, the position of the reference plane

for the radar measurement changes in some cases. This should be

taken into account for the min./max. adjustment. In chapter "Dimen-

sions" of this mounting instructions manual you can find specifications

regarding the reference plane in the dimensional drawings.
Setup is carried out according to the operating instructions manual of

the respective sensor.

False signal suppression

Reference plane