8 Maintenance and fault rectification

VEGABAR 55 • Profibus PA - climate compensated

39442-EN-130321

Error code Cause

Rectification

E113

Communication con-

flict

– Exchange the instrument or send it

in for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8.3 Calculation of total deviation (according to

DIN 16086)

The total deviation F

total

according to DIN 16086 is the sum of basic

accuracy F

perf

and longterm stability F

stab

. F

total

is also called maximum

practical deviation or utility error.
F

total

= F

perf

+ F

stab

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

With the analogue signal output there is also the error of the current

output F

a

.

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

With:

F

total

: Total deviation

F

perf

: Basic accuracy

F

stab

: Long-term drift

F

T

: Temperature coefficient (influence of medium or ambient

temperature)

F

Kl

: Deviation

F

a

: Error current output

Pressure measurement in the pipeline 8 bar (800 KPa)
Product temperature 50 °C, hence within the compensated range
VEGABAR 55 with measuring range 10 bar
Calculation of the set Turn Down: TD = 10 bar/8 bar, TD = 1.25
Basic accuracy digital output signal in percent:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.05 % + 0.1 % x TD)

F

Kl

= 0.075 %

F

perf

= √((0.05 % + 0.1 % x 1.25)

2

+ (0.075 %)

2

)

F

perf

= 0.19 %

Total deviation digital output signal in percent:

F

total

= F

perf

+ F

stab

F

stab

= (0.1 % x TD)/year

F

stab

= (0.1 % x 1.25)/year

F

stab

= 0.125 %

F

total

= 0.19 % + 0.125 % = 0.315 %

Reaction after fault recti-

fication

Total deviation

Example