4 exchanging the electronics module, 5 software update – VEGA VEGABAR 55 Profibus PA - climate compensated User Manual

Page 43

Advertising
background image

43

8 Maintenance and fault rectification

VEGABAR 55 • Profibus PA - climate compensated

39442-EN-130321

Total deviation digital output signal absolute:

F

total

= 0.315 % x 8 bar/100 % = 25.2 mbar

Basic accuracy analogue output signal in percent:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.05 % + 0.1 % x TD)

F

Kl

= 0.075 %

F

a

= 0.15 %

F

perf

= √((0.05 % + 0.1 % x 1.25)

2

+ (0.075 %)

2

+ (0.15 %)

2

)

F

perf

= 0.24 %

Total deviation analogue output signal in percent:

F

total

= F

perf

+ F

stab

F

stab

= (0.1 % x TD)/year

F

stab

= (0.1 % x 1.25)/year

F

stab

= 0.125 %

F

total

= 0.24 % + 0.125 % = 0.365 %

Total deviation analogue output signal absolute:

F

total

= 0.365 % x 8 bar/100 % = 29.2 mbar

8.4 Exchanging the electronics module

In case of a defect, the electronics module can be exchanged by the

user against an identical type. If no electronics module is available on

side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial

number. The electronics module with serial number includes order-

specific data such as factory setting, seal material etc. These are not

included in the electronics module without serial number.
The serial number is stated on the type label of VEGABAR 55 or on

the delivery note.

8.5 Software update

The software version of VEGABAR 55 can be determined as follows:

on the type label of the electronics

Via the display and adjustment module

via PACTware

You can view all software histories on our website www.vega.com.

Make use of this advantage and get registered for update information

via e-mail.
The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

VEGACONNECT

PC with PACTware

Current sensor software as file

Advertising