8 Maintenance and fault rectification

VEGABAR 52 • Foundation Fieldbus

36720-EN-130321

Error

Cause

Rectification

Measured val-

ue on the display

and adjustment

module does not

correspond to the

value in the PLC

The menu item

"Display - Display

value" is not set to

"AI-Out"

Check values and correct, if neces-

sary

Instrument does

not appear during

connection setup

Profibus DP cable

pole-reversed

Check cable and correct, if necessary

Incorrect termi-

nation

Check termination at the beginning

and end points of the bus and termi-

nate, if necessary, according to the

specification

Instrument not

connected to the

segment

Check and correct, if necessary

In Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

Error code Cause

Rectification

E013

no measured value

available

8)

– Exchange the instrument or send it

in for repair

E017

Adjustment span too

small

– repeat with modified values

E036

no operable sensor

software

– Carry out a software update or send

instrument for repair

E041

Hardware error, elec-

tronics defective

– Exchange the instrument or send it

in for repair

E113

Communication con-

flict

– Exchange the instrument or send it

in for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8.3 Calculation of total deviation (according to

DIN 16086)

The total deviation F

total

according to DIN 16086 is the sum of basic

accuracy F

perf

and longterm stability F

stab

. F

total

is also called maximum

practical deviation or utility error.
F

total

= F

perf

+ F

stab

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

With the analogue signal output there is also the error of the current

output F

a

.

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

With:

F

total

: Total deviation

Error messages via the

display and adjustment

module

Reaction after fault recti-

fication

Total deviation

8)

Fault message can also appear if the pressure is higher than the nominal

range.