VEGA VEGABAR 52 Foundation Fieldbus User Manual

Page 50

Advertising
background image

50

10 Supplement

VEGABAR 52 • Foundation Fieldbus

36720-EN-130321

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 36.26 psi

725.2 psi

0 psi

0 … 72.52 psi

942.7 psi

0 psi

0 … 145.0 psi

1305 psi

0 psi

0 … 362.6 psi

1885 psi

0 psi

0 … 870.2 psi

2901 psi

0 psi

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+15 … +25 °C (+59 … +77 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

10)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation with absolutely flush process fittings EV, FT

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.05 %

Ʋ Turn down > 5 : 1

< 0.01 % x TD

Deviation with version 0.075 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.075 %

Ʋ Turn down > 5 : 1

< 0.015 % x TD

Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Deviation with absolute pressure measuring range 0.1 bar

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.25 %

Ʋ Turn down > 5 : 1

< 0.05 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span

10)

Incl. non-linearity, hysteresis and non-repeatability.