4 Mounting

VEGABAR 54 • Profibus PA

36729-EN-130321

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

Seal the flange connections according to DIN/ANSI with a suitable,

resistant seal and mount VEGABAR 54 with suitable screws.

Use the seal corresponding to the instrument.

Shift VEGABAR 54 with PMC connection into the socket and

fasten with two screws M8x10.

4.3 Mounting steps, external housing

1. Mark the holes according to the following drilling template
2. Depending on the mounting surface, fasten the wall mounting

plate with 4 screws

90 mm (3.54")

R 3,5 mm

(0.14")

3mm

(0.12")

70 mm (2.76")

8 mm

(0.32")

93 mm (3.66"

)

110 mm (4.33"

)

Fig. 4: Drilling template - wall mounting plate

Tip:

Mount the wall mounting plate so that the cable entry of the socket

housing points downward. The socket housing can be displaced by

180° to the wall mounting plate.

Warning:

The four screws of the socket housing must only be hand screwed. A

torque > 5 Nm (3.688 lbf ft) can damage the wall mounting plate.

Sealing/Screwing in

flange versions

Mounting, socket ver-

sions

Wall mounting