VEGA VEGABAR 54 Profibus PA User Manual

Page 46

Advertising
background image

46

10 Supplement

VEGABAR 54 • Profibus PA

36729-EN-130321

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 1 bar/0 … 100 kPa

35 bar/3500 kPa

0 bar abs.

0 … 2.5 bar/0 … 250 kPa

50 bar/5000 kPa

0 bar abs.

0 … 5 bar/0 … 500 kPa

65 bar/6500 kPa

0 bar abs.

0 … 10 bar/0 … 1000 kPa

90 bar/9000 kPa

0 bar abs.

0 … 25 bar/0 … 2500 kPa

130 bar/13 MPa

0 bar abs.

0 … 60 bar/0 … 6000 kPa

200 bar/20 MPa

0 bar abs.

Nominal measuring ranges and overload capability in psig
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +1.5 psig

+200 psig

-3 psig

0 … +3 psig

+290 psig

-6 psig

0 … +6 psig

+430 psig

-12 psig

0 … +15 psig

+500 psig

-15 psig

0 … +35 psig

+725 psig

-15 psig

0 … +70 psig

+950 psig

-15 psig

0 … +150 psig

+1300 psig

-15 psig

0 … +350 psig

+1900 psig

-15 psig

0 … +900 psig

+2900 psig

-15 psig

-15 … 0 psig

+500 psig

-15 psig

-15 … +25 psig

+700 psig

-15 psig

-15 … +70 psig

+950 psig

-15 psig

-15 … +150 psig

+1300 psig

-15 psig

-15 … +350 psig

+1900 psig

-15 psig

-15 … +900 psig

+2900 psig

-15 psig

-0.7 … +0.7 psig

+200 psig

-3 psig

-1.5 … +1.5 psig

+290 psig

-6 psig

-3 … +3 psig

+430 psig

-12 psig

-7 … +7 psig

+500 psig

-15 psig

Absolute pressure
0 … 15 psi

500 psi

0 psi

0 … 35 psi

700 psi

0 psi

0 … 70 psi

900 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 350 psi

1900 psi

0 psi

Advertising