VEGA VEGABAR 67 Profibus PA User Manual

Page 56

Advertising
background image

56

10 Supplement

VEGABAR 67 • Profibus PA

36743-EN-130321

Ʋ In the compensated temperature

range 0 … +100 °C (+32 … +212 °F)

< 0.05 %/10 K x TD

Ʋ Outside the compensated tempera-

ture range

typ. < 0.05 %/10 K x TD

Thermal change, current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 32: Thermal change, current output

Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to digital HART interface as well as to analogue current output 4 … 20 mA under refer-

ence conditions. Specifications refer to the set span. Turn down (TD) is the relation nominal meas-

uring range/set span.
Long-term drift of the zero signal:

Ʋ For one year

< 0.05 % x TD

Ʋ For five years

< 0.1 % x TD

Ʋ For ten years

< 0.2 % x TD

Ambient conditions
Ambient, storage and transport temperature

Ʋ Version with connection tube

-40 … +80 °C (-40 … +176 °F)

Ʋ Version with suspension cable FEP,

PUR

-20 … +80 °C (-4 … +176 °F)

Ʋ Version with suspension cable PE

-20 … +60 °C (-4 … +140 °F)

Process conditions
The specifications of the pressure stage and product temperature are used as an overview. The

specifications on the type label are applicable.
Process pressure

Ʋ with measuring ranges 0.1 bar

(1.45 psig) or 0.2 bar (2.9 psig)

max. 15 bar (217.6 psig) or max. 20 bar (290 psig)

13)

13)

Limited by the overpressure resistance of the measuring cell.