Status

code

Description according to

Profibus standard

Possible cause

0 x 04

bad - configuration error

– Adjustment error

– Configuration error with PV-Scale (PV-Span too small)

– Unit irregularity

– Error in the linearization table

0 x 0C

bad - sensor failure

– Hardware error

– Converter error

– Leakage pulse error

– Trigger error

0 x 10

bad - sensor failure

– Measured value generation error

– Temperature measurement error

0 x 1f

bad - out of service constant

"Out of Service" mode switched on

0 x 44

uncertain - last unstable value

Failsafe replacement value (Failsafe-Mode = "Last value" and al-

ready valid measured value since switching on)

0 x 48

uncertain substitute set

– Switch on simulation

– Failsafe replacement value (Failsafe-Mode = "Fsafe value")

0 x 4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and

no valid measured value since switching on)

0 x 51

uncertain - sensor; conversion

not accurate - low limited

Sensor value < lower limit

0 x 52

uncertain - sensor; conversion

not accurate - high limited

Sensor value > upper limit

0 x 80

good (non-cascade) - OK

OK

0 x 84

good (non-cascade) - active

block alarm

Static revision (FB, TB) changed (10 sec. active, after the parame-

ter of the static category has been written)

0 x 89

good (non-cascade) - active ad-

visory alarm - low limited

Lo-Alarm

0 x 8a

good (non-cascade) - active ad-

visory alarm - high limited

Hi-Alarm

0 x 8d

good (non-cascade) - active crit-

ical alarm - low limited

Lo-Lo-Alarm

0 x 8e

good (non-cascade) - active crit-

ical alarm - high limited

Hi-Hi-Alarm