3 wiring plan, single chamber housing, 4 wiring plan, double chamber housing – VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 27

Advertising
background image

27

5 Connecting to the bus system

VEGAPULS 67 • Foundation Fieldbus

36534-EN-121011

8. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

9. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

10. Place probably existing indicating and adjustment module back

on

11. Screw the housing cover back on
The electrical connection is hence finished.

5.3 Wiring plan, single chamber housing

1

2

( )

(-)

1

5

0

1

0

1

+

6 7 8

Bus

2
3

4

5

Fig. 27: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output

2 Contact pins for the indicating and adjustment module or interface adapter

3 Simulation switch ("1" = mode for simulation release)

4 For external indicating and adjustment unit

5 Ground terminal for connection of the cable screen

5.4 Wiring plan, double chamber housing

5

0

1

0

1

+

6 7 8

Bus

2
3

1

2

( )

(-)

1

1

Fig. 28: Electronics compartment, double chamber housing
1 Internal connection to the connection compartment

2 Contact pins for the indicating and adjustment module or interface adapter

3 Simulation switch ("on" = simulation mode)

Electronics and connec-

tion compartment

Electronics compartment

Advertising