4 Mounting

VEGAPULS 67 • 4 … 20 mA/HART - four-wire

36532-EN-121011

– Angle of inclination in three steps 0°, 90° and 180°

Double chamber housing

– Angle of inclination 90°, infinitely variable

– Angle of inclination in two steps 0° and 90°

Fig. 7: Adjustment of the angle of inclination

Fig. 8: Turning by fastening in the centre

4.4 Instructions for installation

For tight installation of the version with plastic horn antenna with com-

pression or adapter flange, the following conditions must be fulfilled:
1. Use suitable flat seal, e.g. of EPDM with Shore hardness 25 or 50
2. Make sure the number of flange screws corresponds to the num-

ber of flange holes

3. Tighten all screws with the torque stated in the technical data

The emitted radar impulses of the radar sensor are electromagnetic

waves. The polarisation plane is the direction of the electrical wave

component. By turning the instrument in the connection flange or

mounting boss, the polarisation can be used to reduce the effects of

false echoes.
The position of the polarisation level is marked by markings on the

instrument.

1

Fig. 9: Position of the polarisation level
1 Marking bar

Tight installation of the

plastic horn antenna

Polarisation plane