7 Setup with PACTware

VEGAPULS 67 • 4 … 20 mA/HART - four-wire

36532-EN-121011

7 Setup with PACTware

7.1 Connect the PC

3

1

2

Fig. 34: Connection of the PC directly to the sensor via the interface adapter
1 USB cable to the PC

2 Interface adapter VEGACONNECT 4

3 Sensor

Information:

The interface adapter VEGACONNECT 3 is not suitable for connec-

tion to the sensor.

1

5

2

4

3

OP

EN

TWIST

USB

LOCK

Fig. 35: Connecting the PC via HART to the signal cable
1 VEGAPULS 67

2 HART resistance 250 Ω (optional depending on processing)

3 Connection cable with 2 mm pins and terminals

4 Processing system/PLC/Voltage supply

Necessary components:

VEGAPULS 67

PC with PACTware and suitable VEGA DTM

VEGACONNECT 4

HART resistance approx. 250 Ω

Via the interface adapter

directly on the sensor

Connection via HART