VEGA VEGAFLEX series 60 Recurring function test User Manual

Page 6

Advertising
background image

Information:
Document the recurring function test, for example, in the test protocol
in the supplement.

The following conditions must be fulfilled when performing the
recurring function test:

0

0

V

dB

3

1

2

Fig. 1: Level echo - VEGAFLEX
1

Echo curve

2

Logarithmic echo curve

3

Amplitude of the useful echo (logarithmic echo curve)

l

The process conditions must be nearly constant (level, process
pressure, process temperature)

l

The medium must be the same as during setup or the medium
must at least belong to the same product group.

-

Solvents/Liquid gases/Hydrocarbons/Oils (DK value < 3)

-

Chemical mixtures (DK value 3 … 10)

-

Water/Acids/Bases (DK value > 10 or conductive)

l

The level must be either in the following areas:

-

Distance to the process fitting ≥ 200 mm.

-

Min. covering of the rod electrode ≥ 100 mm/cable electrode
≥ 250

mm.

-

-

or the following requirement must be fulfilled:

-

-

Reliability at least 20 dB (amplitude of the useful logarithmic
echo above the noise level). The reliability can be verified
during the test.

6

Recurring function test • for VEGAFLEX series 60

2 Prerequisites

36552

-EN