9 supplement, 1 technical data, 9supplement – VEGA VEGABAR 12 User Manual

Page 17

Advertising
background image

9

Supplement

9

.1 Technical data

General data

Parameter, pressure

Gauge pressure

Measuring principle

Ceramic-capacitive, dry measuring cell

Communication interface

Standard interface

Materials and weights

Materials, wetted parts

-

Process fitting

316L

-

Diaphragm

sapphire ceramic

®

(99.9 % oxide ceramic)

-

Measuring cell seal

FKM

Materials, non-wetted parts

-

Electronics housing

316L

-

Connection terminals

PA

-

Ohmic contact

Between ground terminal, housing and process
fitting

Torque max.

20 Nm (14.75 lbf ft)

Weight approx.

0.1 kg (0.22 lbs)

Output variable

Output signal

4 … 20 mA

Fault signal

3,6 mA

Max. output current

22 mA

Step response time

160 ms (0 … 63 %)

Input variable

Adjustment

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

-

zero

-20 … +20 %

-

span

20 … +120 %

Max. turn down

5 : 1

Nominal measuring ranges and overload resistance

The overload specifications are only an overview and refer to the measuring cell. Limitations by
material and process fitting version are possible. The specifications on the type label are
applicable.

VEGABAR

12

17

9 Supplement

35544

-

EN

-110616

Advertising