VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 59

Advertising
background image

59

11 Supplement

VEGAPULS 63 • Profibus PA

36513-EN-130228

3

4

2

1

Fig. 47: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Length antenna cone

4 Useful measuring range

Standard electronics
Max. measuring range

35 m (114.8 ft)

Recommended measuring range

Ʋ Flange DN 50, 2"

up to 15 m (49.21 ft)

Ʋ Flange DN 80, 3"

up to 35 m (114.8 ft)

Electronics with increased sensitivity
Max. measuring range

75 m (246.1 ft)

Flange DN 50, 2"

up to 15 m (49.21 ft)

Flange DN 80, 3"

up to 35 m (114.8 ft)

Output variable
Output signal

digital output signal, format according to IEEE-754

Sensor address

126 (default setting)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Profibus PA profile

3.02

Number of FBs with AI (function blocks

with analogue input)

3

Default values

Ʋ 1. FB

PV

Ʋ 2. FB

SV 1

Ʋ 3. FB

SV 2

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

Ʋ Ex d instruments

16 mA, ±0.5 mA

Resolution, digital

< 1 mm (0.039 in)