VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 63

Advertising
background image

63

11 Supplement

VEGAPULS 63 • Profibus PA

36513-EN-130228

Wire cross-section (spring-loaded terminals)

Ʋ Massive wire, cord

0.2 … 2.5 mm² (AWG 24 … 14)

Ʋ Stranded wire with end sleeve

0.2 … 1.5 mm² (AWG 24 … 16)

Electromechanical data - version IP 66/IP 68 (1 bar)
Options of the cable entry

Ʋ Cable gland with integrated connec-

tion cable

M20 x 1.5 (cable: ø 5 … 9 mm)

Ʋ Cable entry

½ NPT

Ʋ Closing cap

M20 x 1.5; ½ NPT

Connection cable

Ʋ Wire cross-section

0.5 mm² (AWG 20)

Ʋ Wire resistance

< 0.036 Ω/m

Ʋ Tensile strength

< 1200 N (270 lbf)

Ʋ Standard length

5 m (16.4 ft)

Ʋ Max. length

180 m (590.6 ft)

Ʋ Min. bending radius

25 mm (0.984 in) with 25 °C (77 °F)

Ʋ Diameter approx.

8 mm (0.315 in)

Ʋ Colour - Non-Ex version

Black

Ʋ Colour - Ex-version

Blue

Display and adjustment module
Display element

LC display with DOT matrix and backlight

Measured value indication

Ʋ Number of digits

5

Ʋ Size of digits

W x H = 7 x 13 mm

Adjustment elements

4 keys

Protection rating

Ʋ unassembled

IP 20

Ʋ mounted into the housing without

cover

IP 40

Materials

Ʋ Housing

ABS

Ʋ Inspection window

Polyester foil

Integrated clock
Date format

Day.Month.Year

Time format

12 h/24 h

Time zone Ex factory

CET

Measurement electronics temerature
Resolution

1 °C (1.8 °F)

Accuracy

±1 °C (1.8 °F)

Advertising