4 Mounting

VEGAPULS 62 • 4 … 20 mA/HART - two-wire

36503-EN-121011

max. 50 mm (1.97"

)

1

2

3

Fig. 21: Mounting of the instrument with insulated vessels.
1 Electronics housing

2 Distance piece

3 Vessel insulation

The short examples give you introductory information on the flow

measurement. Detailed planning information is available from flume

manufacturers and in special literature.

3 ... 4 h

max

≥ 50 mm

90°

2

3

1

h

ma

x

d

mi

n

≥ 2 mm x

h

ma

x

90°

4

2

3

Fig. 22: Flow measurement with rectangular flume: d

min.

= min. distance of the

sensor (see chapter "Technical data"); h

max.

= max. filling of the rectangular

flume
1 Overflow orifice (side view)

2 Headwater

3 Tail water

4 Overfall orifice (view from bottom water)

In general, the following points must be observed:

Install the sensor on the headwater side

Installation in the centre of the flume and vertical to the liquid

surface

Distance to the overfall orifice

Distance of orifice opening above ground

Min. distance of the orifice opening to bottom water

Min. distance of the sensor to max. storage level

Flow measurement with

rectangular flume