11 Supplement

VEGAPULS 62 • 4 … 20 mA/HART - two-wire

36503-EN-121011

Max. output current

22 mA

Starting current

≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on

Load

see load diagram under Power supply

Damping (63 % of the input variable),

adjustable

0 … 999 s

HART output values according to HART 7.0

1)

Ʋ PV (Primary Value)

Distance to the level

Ʋ SV (Secondary Value)

Level as percentage value

Ʋ TV (Third Value)

Linearised percentage value

Ʋ QV (Fourth Value)

Scaled measured value

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Largest false echo 20 dB smaller than the useful echo

Deviation with liquids

See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

- 10 mm (- 0.394 in)

0

1 2

3

Fig. 56: Deviation under reference conditions
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Reproducibility

≤ ±1 mm

Deviation with bulk solids

The values depend to a great extent on the application.

Binding specifications are thus not possible.

Variables influencing measurement accuracy
Specifications apply to the HART signal and the current output

1)

Default values, can be assigned individually